Deficiency 165466 – Ricketts Dormitory (building 2)
Findings – The ceiling on the first-floor student lounge has approximately 100 SF of black mold on it. A condensate drain in the PTAC unit in the lounge above it has been draining into the ceiling space above the mold.
Recommendations – Cordon off the room with Do Not Enter signage. Using PPE, required mitigation measures, and isolating the area, remove approximately 100 SF of affected drywall. Clean, inspect, and dry the structure above the affected ceiling area. Install new drywall finish and paint to match surrounding ceiling.
Deficiency 165811 – Sewage Treatment Lab (building 120)
Findings – Due to non-operational relays two aerator blowers (#1 and #3) and one digester blower (#1) are controlled by manual mode.
Recommendations – Replace non-operational relays and make all necessary corrections to operate all equipment in the automatic mode (auto control).
Additional Information – Davis Bacon wages apply. Certified payroll required. Please separate labor and materials on bids.